top of page
Description

Aux Cooling Water Pumps

The auxiliary cooling water pumps circulate water in a closed loop that serves as a method of cooling major equipment in the plant. The pumps are single stage centrifugal pumps sized for 50% of the design heat load but configured for all three to operate with variable speed drives that adjust speed to maintain a constant discharge pressure. If one pump is removed from service, the remaining two would increase speed to maintain the system at full capacity, thus adding redundancy to the system.

Specifications

Specifications

Number of Pumps: 3 ea.
Pump Size (HP): 200 HP
Coolant Flow Rate: 8,400 gpm